Choretime 2912 HLC Instructions
CHORE-TIME INSTALLATION INSTRUCTIONS - PARTS LIST
 
2912 Hopper Level Control
INTRODUCTION
The #2912 Hopper Level Control is designed for use with
any conveying system that carries free flowing feed.
The Control automatically starts and stops the fill
system as the feed level against the paddle changes.
The #2912 Control
may be used with or without the high
differential shield. The shield increases the feed
differential of the Control by approximately 5 inches,
to reduce short cycling of the delivery system motor.
If
the delivery system operates on demand, without a
time clock, another hopper may empty faster than the
last one. It may be necessary to install a second
#2912 Control in the other hopper to insure an ample
feed supply. Wire the two Controls in parallel so that
either can start the fill system.
INSTALLATION
Install the Control in the last hopper which is located
at the end of the delivery system. Mount it low so
that the feed level will be lower in that hopper than
in the others. The lower feed level will cause the
system to start frequently enough to maintain feed
in every hopper. Position the feed drop tube to deliver
feed into the center of the hopper in front of the
paddle. Position the drop tubes in the other hoppers
high so that they fill up but do not overflow.
Mount the Hopper Level Control vertically, as shown
in Fig. 1, to assure free movement of the switch
paddle. Drill two 9/32" holes at the desired location.
Use the bracket as a guide to determine the hole
spacing.
supplied.
Fasten the bracket in place with the hardware
assembly.
Install the Control in the mounting bracket
ment or
The Control may be removed for switch adjust-
for house clean out.
SWITCH ADJUSTMENT
1. Remove the two hex bolts from this bracket.
2. Turn hex nut counter-clockwise 1 complete
turn.
3. Turn hex nut clockwise until switch clicks.
4. Turn hex
nut counter-clockwise until
switch
clicks again.
5.
Turn hex nut counter-clockwise 1/4 turn.
Figure 1. #2912 Hopper
Level Control
A WARNING
DISCONNECT POWER BEFORE
servicing
Figure 2. Hopper Level Control Wiring
CONNECT TO
DELIVERY SYSTEM
CONTROL UNIT
COM
NO
The
Hopper Level Control
is a single pole double throw
switch with wiring leads con-
nected so that the circuit is
complete (closed) when there is
no feed against the paddle; and
the circuit is broken (open)when
there is feed against the paddle.
Switch Rating:
15 Amp 125-250 V.A.C.
hp. 125 V.A.C.
hp. 250 V.A.C.
HOPPER
LEVEL
CONTROL
MA185F2-488
Choretime 2912 HLC Parts Image
.

KEY

DESCRIPTION

PART NUMBER

1 High Differential Shield CT 24993
2 Paddle Cover (Diaphragm) CT 2708
3 Paddle CT 2709
4 6-32 Hex Nut (2 reqd) CT 771
5 SPDT Switch (Microswitch) CT 2702
6 Frame CT 2711
8 Fabric Retainer (2 reqd) CT 2705
9 Back CT 2707
10 Mounting Bracket CT 2703
11 Switch  Bracket CT 24991
12 Mounting Bracket Assembly CT 2911
13 Cover CT 711
14 Handy Box CT 1145
15 6-32 x 7/8 Screw (2 reqd) CT 1921
16 Grommet CT 24
17 Flat Washer CT 2955-19
18 10-32 Crown Lock Nut CT 6963
19 Spring CT 24992